3.2 DEFINING THE MAINS FREQUENCY
Switch 1 makes it possible to select the frequency delivered by the mains:
Frequency of the power
supplied by the network
3.3 FILTERING LEVEL
Filtering allows the attenuation of fluctuations in the flow displayed and at the current and
frequency outputs. The 8041 sensor can work without or with filtering.
Switch 2 makes it possible to activate or inhibit filtering :
Flow filtering activation
If filtering has been activated, two filtering levels, slow or fast, are available through
Switch 3:
slow (10 to 90% response time = 14 s)
fast (10 to 90% response time = 5 s)
8041
CONFIGURATION
50 Hz
60 Hz
No
Yes
Flow filtering
11
Position of switch 1
OFF
ON
Position of switch 2
OFF
ON
Position of switch 3
OFF
ON