Unless otherwise noted, specifications are warranted over the ambient temperature range of 0 to 40°C
after a 30-minute warm-up. Specifications apply at the output terminals, with local sensing.
Specification
DC Ratings
   Voltage source:
   Current source and sink:
   Power:
Output ripple & noise
    CV peak-to-peak: 2
    CV rms: 3
Load regulation
    Voltage: 4
    Current:
Voltage programming &
measurement accuracy: 5
Current programming &
measurement accuracy: 5
Transient response 6
    Recovery Time:
    Settling band:
1 200/208 Vac input reduces the current and power rating 50%; 200/208 Vac input is only available with firmware rev B.06.03.1003 and up
2 From 20 Hz to 20 MHz (-3dB bandwidth) with resistive load, terminals ungrounded, or either terminal grounded
3 From 20 Hz to 10 MHz (-3dB bandwidth) with resistive load, terminals ungrounded, or either terminal grounded
4 Also applies when remote sensing with a ≤1 V drop per load lead - see
5 Percent of value + offset; at 25°C ±5°C after a 30 minute warm-up; measurement NPLC=1; valid for 1 year, see
with a ≤1 V drop per load lead - see
6 Recovery to within settling band following a step from 40%-90% and 90%-40% of full load at Comp 0, with a 40μs current rise and fall time
Keysight RP7970 & RP7980 Series Operating and Service Guide
RP7971A
0 to 500 V
0 to ±120 A
0 to ±20 kW
0.75 V
150 mV
25 mV
16 mA
0.04% + 40 mV
0.03% + 12 mA
300 µs
5 V
Wire Size
for information about additional load lead voltage drop
RP7972A
0 to 1000 V
0 to ±60 A
0 to ±20 kW
1.5 V
200 mV
50 mV
8 mA
0.04% + 75 mV
0.03% + 6 mA
300 µs
10 V
Wire Size
and
Remote Sense Connections
1 Quick Reference
RP7973A
0 to 2000 V
0 to ±30 A
0 to ±20 kW
3 V
400 mV
100 mV
4 mA
0.04% + 150 mV
0.03% + 3 mA
300 µs
20 V
for additional information
Calibration
Interval;
37