5 SCPI Programming Reference
This command is only active in Table mode; otherwise error -315 is generated.
l
This command is equivalent to sending both SAS:TABL:UPD, then SAS:TABL:SEL.
l
If the SAS:TABL:CURR and SAS:TABL:VOLT commands are sent after the table is activated, the
l
SAS:TABL:ACT command must be sent again to activate the new table values.
[SOURce:]SASimulator:TABLe:SELect 1|2
[SOURce:]SASimulator:TABLe:SELect?
Selects the active table to run from the two tables that have been entered into the SAS system
location. You can only run one active table at a time, Using this command lets you switch between two
active tables without turning off the output of the unit.
Parameter
1 | 2
Selects Table 2: SAS:TABL:SEL 2
This command is only active in Table mode.
l
[SOURce:]SASimulator:TABLe:UPDate 1|2
Validates the data set and updates the specified table in the SAS system. This moves the table data
from the memory location to the SAS system location, but does not select the table for use. To use this
command, you must have previously loaded a table into the memory location of the unit using
SAS:TABL:CURR and SAS:TABL:VOLT.
Parameter
(none)
Updates Table 2: SAS:TABL:UPD 2
This command is only active in Table mode.
l
[SOURce:]SASimulator:TABLe[1|2]:CURRent[:AMPlitude] <current>{,<current>}
[SOURce:]SASimulator:TABLe[1|2]:VOLTage[:AMPlitude] <voltage>{,<voltage>}
These commands set the voltage and current arrays that define the SAS characteristic when Table
mode is selected. Each of these commands must contain a list of voltage or current points, separated
by commas (,). The table lists must satisfy the following requirements:
For each table, the number of points can range from 3 to 1024; however, both tables must contain
l
the same number of points.
The current point values must be monotonically decreasing. Adjacent values are permitted to be
l
equal. The last value must be zero (a range of ±0.3 mA is allowed).
The voltage point values must be strictly monotonically increasing. Adjacent values are NOT per-
l
mitted to be equal. The first value must be zero (a range of ±15 mV is allowed).
232
Typical Return
Typical Return
Keysight RP7970 & RP7980 Series Operating and Service Guide
1 or 2
(none)