Fault diagnosis
Error
Indication of the
LEDs
The device enables the
PWR Green
outputs even though the
OUT Green
motor is running.
ERR Off
The device enables the
PWR Green
outputs too early (motor is
OUT Green
not yet fully at standstill).
ERR Off
The device does not enable
PWR Off
the outputs even though the
motor is fully at a standstill.
PWR Green
The device does not enable
the outputs even though the
ERR Red
motor is fully at a standstill.
with code 1
The device does not enable
PWR Green
the outputs even though the
or
motor is fully at a standstill.
OUT
Green/yellow
PWR Green
The device does not enable
the outputs even though the
OUT Off
motor is fully at a standstill.
ERR Red
with code 2 or 3
The device does not enable
PWR Green
the outputs even though the
OUT Off
motor is fully at a standstill.
ERR Red
with code 4
The device does not enable
PWR Green
the outputs even though the
OUT Off
motor is fully at a standstill.
ERR Red
with code 5
The device does not enable
PWR Green
the outputs even though the
OUT Yellow
motor is fully at a standstill.
ERR Off
Operating instructions
Rectification of the error
➢ Reduce the voltage threshold U
minimum value.
➢ Check the wiring of the measurement inputs.
➢ Reduce the voltage threshold U
➢ If necessary increase the standstill time t
time to enable).
Undervoltage error or internal device error
➢ Disconnect the supply voltage to the MOC3ZA for at
least 3 seconds.
➢ Replace the device if the problem persists.
Undervoltage error
➢ Check the supply voltage.
Standstill has been detected, but the delay time t
not elapsed yet.
➢ Wait until t
has elapsed.
s
If the outputs are not enabled after 6 s at the latest,
then the measurement inputs L1/L2/L3 are probably
occasionally detecting voltage spikes greater than the
U
set. These voltage spikes can be detected by the
an
OUT LED flashing Green/yellow (i.e. illuminated
green and flashing yellow sporadically).
➢ In this case set U
higher.
an
➢ Rectify the interference on the measurement inputs
(possibly use screened cable).
A previous wire break or offset error on L2 or L3 is still
saved (there is no jumper fitted to terminals S2/X1).
➢ Fit a jumper to terminals S2/X1 (disable error
storage).
See also section 8.3.2 "Wire break/offset" on page 68.
The external device monitoring (EDM, contacts S1/X1)
is not closed or a previous EDM error is still saved (no
jumper fitted to terminals S2/X1).
➢ Close the external device monitoring (EDM).
➢ Fit a jumper to terminals S2/X1 (disable error
storage).
See also section 8.3.3 "EDM error" on page 68.
Simultaneity error on measured signals on L2 and L3.
How to reset the error:
➢ Disconnect the supply voltage to the MOC3ZA for at
least 3 seconds.
➢ The simultaneity error will be automatically reset
when the motor starts again (both measurement
inputs L2 and L3 simultaneously receive measured
signals greater than U
).
an
If the simultaneity error is still present:
➢ Check the wiring of the measurement inputs
L1/L2/L3.
See also section 8.3.4 "Simultaneity of the measured
signals" on page 69.
The voltage on the measurement inputs is greater than
the voltage threshold U
set. If the ERR LED continues
an
to remain off after waiting 8 s, the problem is probably
interference or residual voltage (coupled AC) on the
measurement inputs.
➢ Increase the voltage threshold U
If the error is still present or if it is undesirable to
increase U
:
an
➢ Reduce the coupling of interference onto the cables
on the measurement inputs L1/L2/L3, e.g. using
screening, by shortening the cables or laying them
separately.
➢ For this purpose carry out the following test: If you
short circuit the terminals L1/L2/L3 with no power
applied to the motor, the OUT LED must extinguish.