External device monitoring (EDM)

The static external device monitoring monitors whether the positively guided contactors
have dropped out prior to enabling the output circuits. The N/C contacts for the external
device monitoring are connected between S1 and X1.
Operate the terminals S1/X1/S2 with volt-free contacts!
The terminals S1/X1/S2 have no electrical isolation in relation to the measurement circuit
L1/L2/L3. They must therefore be operated with volt-free contacts with isolation to suit
the measurement circuit L1/L2/L3. Otherwise the safe function of the Standstill Monitor
MOC3ZA is not ensured (see chapter 5 "Electrical installation" on page 59).
If external device monitoring (EDM) is not required, a jumper must be fitted to terminals
S1/X1.
t
t
E
E
Standstill time t
s
Test time on switching on PWR
Operating instructions
MOC3ZA
Voltage threshold U
an
Test time for the
input signals
t
= 2 ... 2.5 s
E