3 INSTALLATION
3.3.14 Electrical wiring of transmitter 8025, wall-mounted, 12-30 VDC,
with relay
Before wiring the device, please read § 3.3.1, 3.3.3, 3.3.4 and 3.3.11 care-
fully.
Install the device as described in § 3.2.3. Unscrew the 4 screws of the cover and unscrew
the cable glands. Pass the cables through the cable glands by preferably respecting the
allocation indicated in § 3.3.12.
Connect the terminals according to the pin assignment described below.
- Only manipulate the switch when device is not powered.
- Make sure switch "FLOW SENSOR" is correctly positioned
according to the separate sensor version (see § 3.3.4).
L+ (12-30 VDC)
4-20 mA output
Switch [1]
(see fig. 3.8)
Strap to be removed
if the 4-20 mA output
is used.
Flow sensor
connection
(see § 3.3.11)
Connection of relay 2
(see ex. fig. 3.8)
Fig. 3.18
Wiring of the 8025, wall-mounted, 12-30 VDC, with relays
Connection of the transmitter 8025, wall-mounted, 12-30 VDC, with relays to a
PLC
Connections of the 4-20 mA output and of the pulse output (in NPN or PNP mode wiring)
of the wall-mounted transmitter, 12-30 VDC, with relays are similar to these of the compact
transmitter, 12-30 VDC, with relays and cable glands (see Fig. 3.9 in § 3.3.6).
Pulse output "minus"
L- (0V)
Pulse output "plus"
Without
With
Supply
PULSE
12..30Vdc
OUTPUT
COIL SENSOR
NPN SENSOR
FLOW SENSOR
1
1 PULSE INPUT
COIL
2
2 -
SUPPLY
3 NC
3 +
4 NC
4 NC
1
2
3
4 PE
Relay cables must be fitted here to the
board using the supplied cable clips
(see § 3.3.3)
E-28-
FLOW TRANSMITTER 8025
Connect the power supply cable shielding
Switch "Sensor Type" :
see § 3.3.4
NPN
Connection of
relay 1 (see
ex. fig. 3.8)