4 CONFIGURATION
4.3.8 Totalizer
The main and daily totalizers are reset in this menu. The reset procedure only starts when
Enter is pressed, at the "END" position in the parameter definition menu.
ENTER
TOTAL
ENTER
CODE
4.4 Test Menu: Press
The following compensations and tests are carried through in the test menu:
OFFSET
SPAN
FREQUENC
FLOW
END
4.4.1 Offset-compensation
Here, the customer has the option to correct the basic setting of 4 mA. He only needs one
current meter. When Enter is pressed while "OFFSET" is displayed, the transmitter produc-
es 4 mA. If this value is incorrect, it can be corrected by entering the measured value.
ENTER
OFFSET
ENTER
SPAN
RES NO
RES YES
ENTER
simultaneously for 5 seconds
0......9
Zero-compensation (4 mA).
Span-compensation (20 mA).
Indication of sensor frequency.
Entering the flow rate to be simulated.
Return to the operation mode and storage of new parameters for
OFFSET and SPAN. If one of the two values is erroneous, the
device point on "OFFSET", and new values must be entered.
OF = 4.00
0......9
OF = 4.02
Entering the measured value
E-38-
FLOW TRANSMITTER 8025