3 INSTALLATION
3.3.9 Electrical wiring of transmitter 8025, panel-mounted, 12-30 VDC,
without relay
Before wiring the device, please read § 3.3.1, 3.3.3, 3.3.4 and 3.3.11 care-
fully.
Install the transmitter as described in § 3.2.2. Connect the terminals acording to the pin
assignment described below.
- Only manipulate the switch when device is not powered.
- Make sure switch "FLOW SENSOR" is correctly positioned
according to the separate sensor version (see § 3.3.4).
Not connected
Flow sensor connection
(see § 3.3.11)
Fig. 3.14
Wiring of the 8025, panel-mounted, 115/230 VAC, without relay
Connection of transmitter 8025, panel-mounted, 12-30 VDC, without relay to a
PLC
Connections of the 4-20 mA output and of the pulse output (in NPN or PNP mode wiring)
of the panel-mounted transmitter, 12-30 VDC, without relay, are similar to these of the com-
pact transmitter, 12-30 VDC, without relay, with cable glands (see Fig. 3.7.in § 3.3.5).
L- (0V)
L+ (12-30 VDC)
Without
With
Supply
PULSE
12..30Vdc
OUTPUT
COIL SENSOR
NPN SENSOR
1
1 PULSE INPUT
2
2 -
SUPPLY
3 NC
3 +
4 NC
4 NC
1
2
3
4 PE
E-24-
FLOW TRANSMITTER 8025
Pulse output "minus"
Pulse output "plus"
Connect the shielding of the power supply cable
Switch "Sensor Type" :
see § 3.3.4
FLOW SENSOR
COIL
NPN