4 OPERATION

4.3.8 Totalizer

The main and daily totalizers are reset in this menu. The reset procedure only starts when
Enter is pressed, at the "END" position in the parameter definition menu.
ENTER
TOTAL
CODE
ENTER
4.4 Test Menu: Press
The following compensations and tests are carried through in the test menu:
OFFSET
SPAN
FREQUENC
FLOW

4.4.1 Offset-compensation

The option to correct the basic setting of 4 mA. A currentmeter is necessary. When Enter
is pressed while "OFFSET" is displayed, the transmitter produces 4 mA. If this value is
incorrect, it can be corrected (within the limit of -0,2; +1 mA) by entering the measured
value.
ENTER
OFFSET
ENTER
SPAN
8035
RES NO
RES YES
0......9
Zero-compensation (4 mA).
Span-compensation (20 mA).
Indication of sensor frequency.
Entering the flow rate to be simulated. The outputs will react
in accordance to this input.
Return to the operation mode and storage of new parameters for
END
OFFSET and SPAN. If one of the two values is erroneous, the
device point on "OFFSET", and new values must be entered.
OF = 4.00
0......9
OF = 4.02
FLOW TRANSMITTER 8035
ENTER
simultaneously for 5 seconds
Entering the measured value
E-21-