11.2

Min. intake pressure

The max. suction head H is calculated as follows:
H = p
x 10.2 – NPSH – H
b
Key:
p
=
Barometric pressure in bar
b
(In certain situations the barometric pressure may be 1 bar). In sealed systems, pb
indicates the system pressure in bar)
NPSH
=
Net positive suction head in mH
(Taken as the figure at the pump's maximum delivery rate given on the NPSH graph
in Appendix B)
H
=
Frictional loss in the intake pipe in mH
f
H
=
Vapour pressure in mH
v
T
=
Fluid temperature
m
H
=
Safety allowance of 0.5 to 1.0mH
s
If the calculated suction head is positive, the pump can operate at the corresponding suction head
of max. "H" mH
O. If the calculated suction head is negative, a supply pump head of at least min.
2
"H" mH
O is required. The calculated head must be available continuously during operation.
2
Example:
Pump type:
Delivery rate:
Fluid temperature:
NPSH:
p
=
1bar
b
H
=
1m chosen
s
H
=
3.0mH
f
H
=
7.2mH
v
H
=
pb x 10.2 – NPSH – H
H
=
1 x 10.2 – 1.1 – 3.0 – 7.2 – 0.5 = 1.6mH
The result means that a suction head of max. 1.6mH
– H
– H
f
v
s
O (see Appendix D)
2
HP-E – ...
15m³/h
+90°C
1.1mH
O (taken from Appendix B)
2
O
2
O (taken from Appendix D)
2
– H
f
Fig. 26 Schematic diagram of maximum suction head
H of an open vented system
O
2
O
2
O
2
– H
v
s
O
2
O during operation is permissible.
2
English
31
|