Electrical Wiring, Compact Version, 115/230 Vac - Burkert 8025 Notice D'utilisation

Masquer les pouces Voir aussi pour 8025:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3 INSTALLATION

3.3.5 Electrical wiring, compact version, 115/230 VAC

- Before wiring the device, please read § 3.3.1, 3.3.2 and 3.3.3 carefully.
- This version does not enable the controller power supply to be used
for inputs IN1 to IN4 and output OUT.
Lift the transparent lid after having unfastened the screw. Remove the cover of the device
by unscrewing the 4 screws, pass the cables through the cable glands and connect
according to the pin assignment below.
Always seal the unused cable gland using the supplied obstructor to
ensure the tightness of the device.
Unscrew the cable gland nut, insert the obstructor and screw the nut
back onto the cable gland.
Only manipulate the switches when the device is not powered.
Connect the shielding of IN binary inputs and OUT output
cable
"Batch status indication" output
Binary inputs, volume selection
Fit here the cables using the
supplied cable clips
(see § 3.3.2)
Not used
Fig. 3.7
Electrical wiring 8025, compact version, 115/230 VAC
Common
{
1 2 3 4 5 6 7 8 9 10 11
NPN SENSOR
BINARY
1 PULSE INPUT
2 -
SUPPLY
3 +
4 NC
COIL SENSOR
NC
1
2
3
4 PE
L+
SENSOR SUPPLY
3A/230VAC
FLOW SENSOR
Connect relay 2
(see ex. fig. 3.8)
Relay cables must be fitted here
to the board using the supplied
cable clips (see § 3.3.2)
E-17-
BATCH CONTROLLER 8025
red wire *
black wire *
yellow wire *
Selection of the 115 or 230 VAC
power supply
Supply
12..30Vdc
COIL
NPN
SENSOR INPUT
(L+)-12V
L
N
Connect relay 1
(see ex. fig. 3.8)
* wired ex-works
see § 3.3.3
125 mA
PE
Fuse
Connect the
115/230 VAC
power supply

Publicité

Table des Matières
loading

Table des Matières