4 CONFIGURATION

4.4.5. Overfill correction

The 8025 Batch Controller has a jet correction facility. It memorises the fluid quantity
which continues to flow after the closure of the valve so that it can be deducted from the
following dosage. In this sub-menu the user enables or disables the jet correction facility.
OVERFILL
ENTER
ALARM
ENTER
4.4.6 Alarm
The menu makes it possible to enable or disable the trigger-off of the alarm during a
dosage (DURING option) and/or after a dosage (AFTER option). It also makes it possible
to program the time delay before the alarm is triggered off, for either option. The alarm
display prompt is «ALARM». This alarm data prompt is also available on tag strip terminal
N°. 5 (transistor output, open collector) and on Relay N° 2 if this relay has been configured
as an alarm relay (see next paragraph).
For the conditions required to trigger off the alarm, see Section 5.
Range of adjustment: between 0 and 999 seconds.
ALARM
ENTER
RELAY
NOTE : The time delay before the alarm is triggered off must take into account the overfill
correction if enabled.
OVERF. N°
OVERF. Y
DURING
ENTER
AFTER
ENTER
E-35-
BATCH CONTROLLER 8025
ON
ENTER
OFF
ENTER
ON
ENTER
OFF
ENTER
DEL1 =
000
0......9
DEL1 = 015
ENTER
DEL2 =
000
0......9
DEL2 = 015
ENTER