Electrical Data - Burkert 8692 Guide Rapide

Masquer les pouces Voir aussi pour 8692:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8692, 8693
Technicaldata
6.8
Electrical data
WARNING!
Only circuits with limited power may be used for UL approved
components according to "NEC Class 2".
Protection class
3 as per DIN EN 61140 (VDE 0140-1)
Connections
Cable gland M16 x 1.5, SW22
(clamping area 5 ... 10 mm)
with connection terminals for cable cross-
sections 0.14 ... 1.5 mm² (24 V DC) or
circular plug-in connector (M12 x 1)
(24 V DC, PROFIBUS DP, DeviceNet)
Operating voltage
24 V DC ± 10 % - max. residual ripple 10 %
Power consumption < 5 W
Input data for actual value signal
4 ... 20 mA:
Input resistance
Resolution
Frequency:
Measurement range 0 ... 1000 Hz
Input resistance
Resolution
Input signal
Waveform
Pt 100:
Measurement range -20 ... +220 °C
Resolution
Measurement current < 1 mA
Input data for set-point value signal
Analogue feedback
Inductive
proximity switches
Binary outputs
180 Ω
Binary input
12 bit
17 kΩ
1‰ of measurement
Communication
value
interface
> 300 mVss
sine, square, triangle
Communications
software
< 0.1 °C
0/4 ... 20 mA:
Input resistance
Resolution
0 ... 5/10 V:
Input resistance
Resolution
Max. current
10 mA
(for voltage output 0 ... 5/10 V)
0 ... 560 Ω
Burden (load)
(for current output 0/4 ... 20 mA)
100 mA current limitation
galvanically isolated, PNP
Current limitation
100 mA, output is clocked if overload
occurs
galvanically isolated, PNP
0 ... 5 V = log "0", 10 ... 30 V = log "1"
inverted input in reverse order
(input current < 6 mA)
Direct connection to PC via USB adapter
with integrated interface driver
Communicator
English
180 Ω
12 bit
19 kΩ
12 bit
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

8693

Table des Matières