5 MAINTENANCE

5.1 Fault prompts

5.1.1. «ALARM» prompt
"ALARM" PROMPT DURING A DOSAGE
The «ALARM « prompt will be displayed during a dosage operation (irrespective of the
dosage option) if one or both valves are open but the controller does not detect any flow.
The time delay before triggering the alarm is set in the Calibration menu. (see § 4.4.6).
A dosage that has been stopped by the alarm can either be continued or cancelled:
a) Manual or automatic dosage activated by LOC.MANU, LOC.MEM or MEM+MANU:
ALARM
* When in mode MEM+MANU, LOC.MEM or LOC.MANU, you can also start the dosage
using the 'Start/Pause' Binary Data Input.
b) Dosage through Binary Inputs and activated by EXT.MEM :
1
ALARM
2
3
Place the Binary
Inputs to 0
(**) When in mode EXT.MEM or EXT [T], you can also press the Enter key on the keypad.
CONTINUE
ENTER
**
then
4
BATCH CONTROLLER 8025
ENTER
*
RESET
Device ready for a new batch (see
ENTER
4.3.1 or 4.3.2)
*
4
**
RESET
OR
1
2
3
Place the Binary Inputs to
the position of the current
dosage
E-40-
Current batch
continues
Device ready for a new
batch (see 4.3.2)
CONTINUE
Current batch
continues
**
4