Technicaldata
6.7
pneumatic data
Control medium: neutral gases, air
Quality classes in accordance with ISO 8573-1
Dust content
Class 7:
Water content Class 3:
Oil content
Class X:
Temperature range
control medium:
Pressure range
control medium:
Air output of pilot valve:
Connections:
23xx / 2103 (Element):
Model third-party device:
Type 8696
max. particle size 40 µm,
max. particle density 10 mg/m³
max. pressure dew point
- 20 °C or min. 10 °C below the
lowest operating temperature
max. 25 mg/m³
-10 – +50 °C
3 – 7 bar
7 l
/ min (for aeration and deaeration)
N
(Q
- value according to definition for
Nn
pressure drop from 7 to 6 bar absolute)
Plug-in hose connector ∅ 6mm / 1/4"
Socket connection G 1/8
Socket connection G 1/8
with M5 connection for connecting to
the third-party device
6.8
electrical data
Warning!
Only circuits with limited power may be used for UL approved
components according to "NEC Class 2".
Connections
Pilot valve
Supply voltage
Power input
Input resistance
for set-point value signal
Protection class
Analogue position feedback
max. load for current output
0/4 – 20 mA
Binary input
Communications
interface
english
Circular plug-in connector
(M12 x 1, 8-pole)
24 V DC ± 10%
- max. residual ripple 10 %
≤ 3.5 W
180 Ω at 0/4 – 20 mA /
12 bit resolution
3 as per DIN EN 61140 (VDE 0140-1)
560 Ω
0 – 5 V = log "0",
12 – 30 V = log "1"
inverted input in reverse order
Direct connection to PC via USB
adapter with integrated interface
driver, communication with communi-
cations software.
11