installation and wiring
Installationandwiring
Load
Power cable shield
(solenoid valve,
for example)
-
+
-
+
Power supply
12-36 V DC
Fig. 13:
NPN wiring of the transistor output of a version with
EN 175301-803 fixed connector
Load
Power cable shield
(solenoid valve,
for example)
-
+
-
+
Power supply
12-36 V DC
Fig. 14:
PNP wiring of the transistor output of a version with
EN 175301-803 fixed connector
(*) Functional earth
(*)
1
V+
PNP transistor
3
2
output
0 V DC
(*)
1
V+
NPN transistor
output
3
2
0 V DC
7.3.3.
Wiring a version with 2 transistor
outputs and a 5-pin m12 male fixed
connector
danger
risk of injury due to electrical voltage
• Always plug in and tighten the connectors correctly.
4
3
5
1
2
The position of the 5-pin M12 fixed connector is adjustable:
→
Unscrew the locknut.
→
Turn the fixed connector to the desired position, by 360° max. to
prevent the cables from twisting inside the housing.
→
Tighten the locknut using a spanner, while keeping the fixed
connector in the desired position.
Fig. 15:
Allocation of the pins on the 5-pin M12 fixed connector
English
1: V+ (12-36 V DC)
2: NPN transistor output
3: 0 V DC
4: PNP transistor output
5: Functional earth