Unscrew the nut [1] on the body [4].
4
3
2
1
→
Insert the cable into the nut [1], the cable
clamp [2] and the seal [3], and then into
the body [4].
→
Strip 20 mm of the cable.
5
→
Cut the central wire (earth) so that its
length is equal to 11.5 mm.
→
Expose 5.5 mm of the wires on the
stripped cable.
→
Insert each wire into the appropriate pin
on the terminal block [5] (see chap. 7.3.3
to 7.3.7).
→
Screw the terminal block [5] once wired
to the body [4]
→
Tighten the connector nut [1].
Fig. 11:
Assembling an M12 female connector (not supplied )
18
English
installation and wiring
Installationandwiring
7.3.2.
Wiring a version with transistor
output and en175301-803 male fixed
connector
danger
risk of injury due to electrical voltage
• Always plug in and tighten the connectors correctly.
the device is not tight when the en 175301-803 fixed
connector is not wired:
→
Unscrew the nut [1] (see Fig. 10) on the 2508 female
connector supplied with the device.
→
Insert the plug with order code 444509, supplied with
the device, into the cable gland.
→
Screw the nut again.
→
Plug the sealed 2508 connector onto the
EN 175301-803 fixed connector.
1
2
1
2
3
3
Fig. 12:
Pin assignment of the EN175301-803 fixed connector
1: V+ (12-36 V DC)
2: Transistor output (NPN or PNP)
3: 0 V DC
4: Functional earth