7.4.1.
Assembling the m12 female connector
1
2
Fig. 8:
M12 multi-pin connector (not supplied, ordering code
917116)
7.4.2.
Wiring a version with m12 fixed
connector
note
• For the electrical connection of a version with an M12 fixed con-
nector, use a straight connector.
Not connected
0 VDC
4
3
(*)
5
1
2
V+
NPN pulse output
Version with 1 pulse output
Fig. 9:
Pin assignment of the M12 male fixed connector
(*) Functional earth;
28
→
Completely unscrew the
nut [1]
→
Remove the rear section of
the connector [2].
→
Wire the device (see chap.
7.4.2)
PNP pulse output
0 VDC
4
3
(*)
5
1
2
NPN pulse output
V+
Version with 2 pulse outputs
English
Type 8011
Installationandwiring
pin of the m12 female cable available as
accessory equipment (order code 438680)
1
2
3
4
5
Power supply, 4,5-24 V DC or
4
3
blue
5
white
brown
1
2
Fig. 10: NPN wiring of the pulse output of a version with M12
fixed connector
(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /
50 V capacitor between the negative power supply terminal and the earth.
color of the
wire
brown
white
blue
black
grey
6-36 V DC
+ -
(*)
grey
Load