7.4.1.
Assembling the m12 female
connector
1
2
Fig. 8 : M12 multi-pin connector (not supplied, ordering code
917116)
7.4.2.
Wiring a version with adjustable
m12 fixed connector
Not connected
0 VDC
4
3
(*)
5
1
2
V+
Pulse output
(12-36 VDC)
(NPN by default)
Version with pulse output
Fig. 9 : Pin assignment of the M12 male fixed connector
32
→
Completely unscrew the
nut [1]
→
Remove the rear section of
the connector [2].
→
Wire the device (see chap.
9.2.3)
4-20 mA
0 VDC
4
3
(*)
5
2
1
Pulse output
V+
(NPN by default)
(12-36 VDC)
Version with pulse and current
outputs
English
Type 8012
Installationandwiring
pin of the m12 female cable available as
accessory equipment (order code 438680)
1
2
3
4
5
The M12 fixed connector of the device is adjustable in position:
→
Unscrew the locknut.
→
Turn the fixed connector to the desired position, by 360° max. so
as not to twist the cables inside the enclosure.
→
Tighten the locknut using a spanner, while keeping the fixed
connector in the desired position.
4
3
blue
5
white
brown
1
2
Fig. 10 : NPN wiring (default) of the pulse output of a version with
M12 fixed connector
(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF / 50 V
capacitor between the negative power supply terminal and the earth.
color of the
wire
brown
white
blue
black
grey
12-36 VDC
Power supply
+ -
(*)
grey
Load