Adjustment and functions
Adjustmentandfunctions
Window operation
The change of state is done whenever one of the thresholds is
detected.
Contact
Not inverted
ON
Flow
OFF
rate
OLO OHI
Fig. 36:
Window operation of the transistor output
The time delay (DEL) is valid for both output thresholds. switching
is only done if one of the thresholds (OHI - OLO) is exceeded for a
duration longer than this time delay.
Contact
Inverted
ON
Flow
OFF
OLO OHI
rate
Flow rate
OHI
OLO
OUT
hysteresis operation
ON
Not inverted
OFF
ON
DEL = 0 s
Inverted
OFF
ON
Not inverted
OFF
ON
DEL = 2 s
Inverted
OFF
Window operation
ON
Not inverted
OFF
ON
DEL = 0 s
Inverted
OFF
ON
Not inverted
OFF
ON
DEL = 2 s
Inverted
OFF
Fig. 37:
Examples for the behaviour of the transistor or relay
output of a 8032 / 8072, depending on the flow rate and
the operation chosen.