installation and wiring
Installationandwiring
7.3.4.
Wiring of the version with a single
relay output
Warning
shock hazard due to the voltage at the relay terminals, which
is higher than 48v.
• Before powering the device, always check that the connectors
are correctly plugged-in and tightened.
the device is not tight when the en 175301-803 fixed
connector is not wired:
→
Unscrew the nut [1] (see Fig. 10) on the 2508 female
connector supplied with the device.
→
Insert the plug with order code 444509, supplied with
the device, into the cable gland.
→
Screw the nut back.
→
Plug the sealed 2508 connector onto the
EN 175301-803 fixed connector.
1
2
2
1
3
3
Fig. 19:
Pin assignment on the EN 175301-803 fixed connector
1: Common
2: Relay, normally closed (NC)
3: Relay, normally open (NO)
4: Not connected
4
3
5
1
2
The position of the 5-pin M12 fixed connector is adjustable:
→
Unscrew the locknut.
→
Turn the fixed connector to the desired position, by 360° max. to
prevent the cables from twisting inside the housing.
→
Tighten the locknut using a spanner, while keeping the fixed
connector in the desired position.
Fig. 20:
Pin assignment of the 5-pin M12 fixed connector
pin of the m12 female cable
available as accessory
equipment (order code 438680)
1
2
3
4
5
(1) Use a voltage limiter depending on the load selected, e.g. for the solenoid
valve, an EN 175301-803 connector with integrated varistor.
(*) Functional earth
English
1: V+ (12-36 V DC)
2: not connected
3: 0 V DC
4: not connected
5: Functional earth
colour of the wire (signal)
brown (V+)
not connected
blue (0 V DC)
not connected
grey (functional earth)
21