Wiring Of The Version With A Single Current Output - Burkert 8032 Manuel D'utilisation

Masquer les pouces Voir aussi pour 8032:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

not connected
250 V AC
L
1
N
3
(1)
Relay output, normally open
(NO)
Load
(solenoid valve,
for example)
Fig. 21:
NO wiring of the relay output of a version with one 5-pin
M12 and one EN 175301-803 fixed connectors
not connected
250 V AC
N
L
1
3
(1)
Relay output, normally
closed (NC)
Load
(solenoid valve,
for example)
Fig. 22:
NC wiring of the relay output of a version with one 5-pin
M12 and one EN 175301-803 fixed connectors
22
Power cable shield
blue
4
3
grey
5
1
2
2
brown
Power supply
-
+
12-36 V DC
Power cable shield
blue
4
3
grey
5
1
2
2
brown
Power supply
-
+
12-36 V DC
English
7.3.5.
Wiring of the version with a single
current output
4
5
1
(*)
The position of the 5-pin M12 fixed connector is adjustable:
Unscrew the locknut.
Turn the fixed connector to the desired position, by 360° max. to
prevent the cables from twisting inside the housing.
Tighten the locknut using a spanner, while keeping the fixed
connector in the desired position.
Fig. 23:
Pin assignment of the 5-pin M12 fixed connector
pin of the m12 female cable
a v a i l a b l e a s a c c e s s o r y
equipment (order code 438680)
(*)
The current output can be connected in either sourcing or sinking
mode.
installation and wiring
Installationandwiring
1: V+ (12-36 V DC)
3
2: Negative 4-20 mA output
3: 0 V DC
4: Positive 4-20 mA output
2
5: Functional earth
colour of the wire (signal)
1
brown (V+)
white (negative 4-20 mA
2
3
blue (0 V DC)
4
black (positive 4-20 mA output)
5
grey (functional earth)
output)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

8072

Table des Matières