9.6.1.
Adjusting the 4-20 mA output
3.95
MA
ENTER
OFFS
0......9
*
To the function "END" of the Test menu
• When the function "OFFS" is displayed, the device gives a 4-mA current.
→
Measure the current given on the 4-20 mA output using a multimeter.
→
Enter this value in the function
→
Press ENTER to confirm.
• When the function "SPAN" is displayed, the device gives a 20-mA current.
→
Measure the current given on the 4-20 mA output using a multimeter.
→
Enter this value in the function
• Confirm or do not confirm the values entered by choosing "
values entered is outside the permitted range: see chap. 10.3.
40
20.50
ENTER
ENTER
span
0......9
*
. The permitted offset range is 3 to 5 mA.
OFFS
. The permitted span range is 18,5 to 21,5 mA.
SPAN
English
YES
ENTER
MA
0......9
NO
ENTER
MA
" or "
". When the message "ERR11" is displayed, at least one of the
YES MA
NO MA
Adjustment and functions
Adjustmentandfunctions
yes
ERR 11 ?
* to move the decimal point, simultane-
no
ously press keys
and
0......9