5.3
Calibration with Pressure
5.3.1 Zero Point Calibration
Make sure that the pressure to be used as the zero point (P 0 %), is
present at the transmitterer diaphragm before calibration.
Calibration Value
Zero point calibration
5.3.2 Span Calibration
Calibration of the measurement range (span).
Make sure that the pressure to be used as the span end-point (P 100 %) is
present at the transmitter diaphragm.
Calibration Value
Calibration of span
A change in the zero point has no effect on the calibrated span.
However, if the span end-point is higher than the peak value of the sen-
sor's nominal pressure range, then span end-point is fixed at this peak val-
ue and the span is reduced accordingly.
A change in the span setting has no effect on the zero point. The zero point
and span end-point must fall within the sensor's nominal pressure range.
Subject to technical changes without notice.
Pressure Transmitter 8326
Operation of Devices without Displays
Set
Value
Set
Value
meas
meas
GB-16