4 OPERATION
4.3 Calibration Mode: Press
The following adjustments are set in the calibration mode display:
LANGUAGE
UNIT
CELL CST
T ° COEFF
CURRENT
RELAY
FILTER
END
4.3.1 Language
ENTER
LANGUAGE
ENTER
UNIT
ENTER
Selection between English, German, French or Italian.
Selection of engineering units for conductivity and
temperature.
Enter the sensor cell constant
Selection of temperature compensation mode (linear,
automatic or Teach-in function).
Determination of 4...20 mA measuring range.
Parameter definition of relays. This message only appears if
the relay option has been installed.
Damping selection. There are ten different steps available.
Back to the operation mode and save the new parameters.
ENGLISH
DEUTSCH
FRANCAIS
ITALIANO
E-16-
CONDUCTIVITY 8225
simultaneously for 5 seconds
The selected language is
confirmed by the Enter-key and
becomes immediately active.
8225-COMP-**