5.5
Integration Time (Damping) Adjustment
The following integration time settings can be used: 0, 1, 5, 20 and 40 s.
The sensor's measured values can then be averaged using the adjusted integration
time.
Calibration Value
Calibration of the integration time
5.6
Reset to Default
All default data settings are restored by simultaneously pressing the "zero", "esc" and
the "ok" buttons for 2 seconds (see Para. 6.4).
Calibrated special measurement ranges i. e. 4 bar on a 6 bar transmit-
ter can be adjusted by factory pre-setting. A reset to default will reset
the sensor back to its nominal range (i. e. 6 bar). The factory pre-setting
Important
gets lost.
Subject to technical changes without notice.
GB-19
Pressure Transmitter 8326
Operation of Devices without Displays
Set
Value
Calibration Value