Main Menu: Output - Burkert 8326 Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.5.3 Main Menu: Output

MAIN MENU
OUTPUT
OUTPUT
DEFINITION
OUTPUT
INVERSION
Subject to technical changes without notice.
GB-27
Operation of Transmitters with Displays
DAMPING
DAMPING
DAMPING
DAMPING
OUTPUT
DAMPING
DAMPING
OUTPUT
Output is inverted (20-4 mA)
REVERSION
or reverted (4-20 mA)
OUTPUT
ALARM/ERROR
OUTPUT
LIMITS
LIMITS
LIMITS
OUTPUT
CURRENT OFFSET
Pressure Transmitter 8326
Damping
40 s active
Damping
20 s active
Damping
5 s active
Damping
1 s active
Damping
0 s active
Alarm at 3.6 mA
(downscale)
Alarm at 21 mA
(upscale)
Measured value runs between 3.8 and 20.5 mA.
The current holds at the limit when the sensing range
is exceeded.
The current runs between 4 and 20 mA
Alarm condition when limits are reached; it is necessary
to restart device by using reset or by shutting down power
(see 6.5.6).
The output current is combined with an assigned offset, which
can have a maximum of 0.8 mA.

Publicité

Table des Matières
loading

Table des Matières