4 CONFIGURATION
4.4.5. Overfill correction
The 8035 Batch controller has an overfill correction facility. It memorises the fluid volume
which flows after the closure of the valve so that this volume can be deducted from the next
batch. In this sub-menu the user enables or disables the overfill correction facility.
OVERFILL
ENTER
ALARM
ENTER
4.4.6 Alarm
The menu makes it possible to enable or disable the trigger-off of the alarm during a dosage
(DURING option) and/or after a dosage (AFTER option). It also makes it possible to
program the time delay before the alarm is triggered off, for either option. The alarm display
prompt is «ALARM». This alarm data prompt is also available on tag strip terminal N°. 5
(transistor output, open collector) and on Relay N° 2 if this relay has been configured as an
alarm relay (see next paragraph).
For the conditions required to trigger off the alarm, see Section 5.
ALARM
ENTER
RELAY
Range of adjustment: between 0 and 999 seconds.
Note: The time delay before the alarm is triggered off must take into account the overfill
correction if enabled.
OVERF. NO
OVERF. Y
DURING
ENTER
AFTER
ENTER
E-26-
BATCH CONTROLLER 8035
ON
ENTER
OFF
ENTER
ON
ENTER
OFF
ENTER
DEL1= 000
0......9
DEL1= 015
ENTER
DEL2= 000
0......9
DEL2= 015
ENTER