WARNING!
Risk of injury from improper installation!
▶ Installation may be carried out by authorized technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
uncontrolled restart!
▶ Secure system against unintentional activation.
▶ Following installation, ensure a controlled restart.
11.2 E lectrical installation with circular
plug-in connector
Procedure:
Connect Type 8692/8693 according to the tables.
In designs with proximity switch:
Set the proximity switch (see "11.2.1 Setting the proximity switch
- optional")
When the operating voltage is applied, Type 8692/8693 is
operating.
Now make the required basic settings and adjustments for the
positioner/process controller. For description see Chapter
"13 Start-up".
22
English
Type 8692, 8693
Electricalinstallation
Designation of the circular plug-in connectors:
3
4
5
6
3
4
2
3
4
4
3
Fig. 13: Electrical connection with 24 V DC circular plug-in connector
X1 - M12 circular connector,
2
8-pole
1
Input signals for the control
8
center
7
Output signals from the control
center (optional)
X5 - M8 circular connector,
1
4-pole (only Type 8693)
2
Input signals process actual
value
X6 - M12 circular connector,
1
4-pole
Operating voltage
2
X4 - M8 socket, 4-pole
Option: proximity switch
1
Switch
(to operate loosen the screw
connection)