15 DISASSEMBLY OF TYPE 8692/8693
WARNING!
Risk of injury from improper disassembly!
▶ Disassembly may be carried out by authorized technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
uncontrolled restart!
▶ Secure system against unintentional activation.
▶ Following disassembly, ensure a controlled restart.
Sequence:
1. Remove the pneumatic connections.
2. Disconnect the electrical connection.
3. Remove Type 8692/8693.
36
English
Type 8692, 8693
DisassemblyofType8692/8693
15.1 Disconnecting the pneumatic
connections
DANGER!
Risk of injury from high pressure!
▶ Before loosening lines and valves, turn off the pressure and vent
the lines.
Pneumatic connections
Type 8692/8693
Valve actuator
Type 8692/8693 with
process valve
Type 2103, 2300 or 2301
Fig. 23: Removing the pneumatic connections
→
Disconnect the pneumatic connections to Type 8693/8693.
For process valves belonging to series 26xx and 27xx:
→
Disconnect the pneumatic connections to the actuator.
Pneumatic
connections
Type 8692/8693 with
process valve
of series 26xx or 27xx