Electrical Installation With Cable Gland - Burkert 8692 Guide Rapide

Masquer les pouces Voir aussi pour 8692:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8692, 8693
Electricalinstallation
11.3 E lectrical installation with cable
gland
Procedure:
Loosen the 4 screws of the connection cover and remove the
cover. The connection terminals are now accessible.
Push the cables through the cable gland.
Connect the wires.
Tighten the union nut of the cable gland (tightening torque
approx. 1.5 Nm).
Place the connection cover with inserted seal onto the electrical
connection housing and tighten cross-wise (tightening torque
max. 0.7 Nm).
NOTE!
Damage or malfunction due to ingress of dirt and moisture!
To comply with the degree of protection IP65 / IP 67:
▶ Close all unused cable glands with dummy plugs.
▶ Tighten the union nut of the cable gland.
Tightening torque depends on cable size or dummy plug
approx. 1.5 Nm.
▶ Only screw on connection cover with the seal inserted.
Tightening torque max. 0.7 Nm.
When the operating voltage is applied, Type 8692/8693 is operating.
Now make the required basic settings and adjustments for the
positioner/process controller. For description see Chapter
"13 Start-up".
Connection cover
Fig. 17: Cable gland connection
Terminal Assignment
11
Set-point value +
10
Set-point value GND
14
Operating voltage +
13
Operating voltage
12
Binary input +
13
Binary input GND
9
Analog position feedback +
8
Analog position feedback GND
5
Binary output 1
6
Binary output GND
7
Binary output 2
Tab. 7:
Cable gland connection
English
Switch
1
8
5
12
2
9
6
13
3
10
7
14
4
11
Connection terminals
(0/4 ... 20 mA / 0 ... 5/10 V)
24 V DC
GND