Type 8692, 8693
Electricalinstallation
11.3 E lectrical installation with cable
gland
Procedure:
→
Loosen the 4 screws of the connection cover and remove the
cover. The connection terminals are now accessible.
→
Push the cables through the cable gland.
→
Connect the wires.
→
Tighten the union nut of the cable gland (tightening torque
approx. 1.5 Nm).
→
Place the connection cover with inserted seal onto the electrical
connection housing and tighten cross-wise (tightening torque
max. 0.7 Nm).
NOTE!
Damage or malfunction due to ingress of dirt and moisture!
To comply with the degree of protection IP65 / IP 67:
▶ Close all unused cable glands with dummy plugs.
▶ Tighten the union nut of the cable gland.
Tightening torque depends on cable size or dummy plug
approx. 1.5 Nm.
▶ Only screw on connection cover with the seal inserted.
Tightening torque max. 0.7 Nm.
When the operating voltage is applied, Type 8692/8693 is operating.
→
Now make the required basic settings and adjustments for the
positioner/process controller. For description see Chapter
"13 Start-up".
Connection cover
Fig. 17: Cable gland connection
Terminal Assignment
11
Set-point value +
10
Set-point value GND
14
Operating voltage +
13
Operating voltage
12
Binary input +
13
Binary input GND
9
Analog position feedback +
8
Analog position feedback GND
5
Binary output 1
6
Binary output GND
7
Binary output 2
Tab. 7:
Cable gland connection
English
Switch
1
8
5
12
2
9
6
13
3
10
7
14
4
11
Connection terminals
(0/4 ... 20 mA / 0 ... 5/10 V)
24 V DC
GND