Specify Position Of The Plug-In Jumpers - Burkert 3003 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D MEM pushbutton
E
CLOSE pushbutton
F
OPEN pushbutton
G K1 plug-in jumper
To prevent electromagnetic interference, shielded cables
must be used.
work steps:
Loosen the cable gland and feed the cable through.
Wire the signal transducer between terminals 15 and 16. Terminal
15 is the negative pole (-) and terminal 16 the positive pole (+).
Wire the position feedback sensor between terminals 13 and 14.
Terminal 13 is the positive pole (+) and terminal 14 the negative
pole (-).
Re-attach the cable gland.
If the connection voltage is 100 V to 240 V, a fuse must be
provided in the power supply.
14
K
LED yellow: Indicates the
power supply
L
Potentiometer
M
Motor connection
N
Heat resistor connection
english
Type 3003
Installation
8.6. specify position of the plug-in
jumpers
OFF
ON
Fig. 7:
Plug-in jumper
Fig. 8:
K1 / K2
signal
feed-
plug-in jumper
trans-
back
k1
ducer
a
0-10 V
0-10 V
ON
0-10 V
0-20 mA
ON
0-10 V
4-20 mA
ON
0-20 mA
0-10 V
OFF
0-20 mA
0-20 mA
OFF
0-20 mA
4-20 mA
OFF
4-20 mA
0-10 V
OFF
4-20 mA
0-20 mA
OFF
4-20 mA
4-20 mA
OFF
Plug-in
Fig. 9:
Plug-in
jumper K3
jumper K3
OFF
ON
plug-in jumper
plug-in
k2
jumper
k3
b
a
b
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON

Publicité