Burkert 8692 Guide Rapide page 30

Masquer les pouces Voir aussi pour 8692:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

X5 - M 8 circular connector, 4-pole
(process actual value) - only Type 8693
Input
Wire
Pin
Assignment
type **
color*
4 ... 20 mA
1
brown
+ 24 V supply Transmitter
- internally
2
white
output of transmitter
supplied
3
blue
GND
4
black
bridge after GND
4 ... 20 mA
1
brown
not assigned
- externally
2
white
Process actual +
supplied
3
blue
not assigned
4
black
Process actual -
Frequency
1
brown
+ 24 V sensor supply
- internally
2
white
Clock input +
supplied
3
blue
Clock input - (GND)
4
black
not assigned
Frequency
1
brown
not assigned
- externally
2
white
Clock input +
supplied
3
blue
Clock input -
4
black
not assigned
Pt 100
1
brown
not assigned
(*** see
2
white
Process actual 1 (current feed)
note)
3
blue
Process actual 3 (GND)
4
black
Process actual 2 (compensation)
*
The indicated colors refer to the connection cable available as an
accessory (92903474).
** Can be adjusted via software (see operating instructions
Type 8692/8693 "Setting up the process controller").
Tab. 11: X5 - M8 circular connector, 4-pole (process actual value) -
Type 8693
30
Switch
Switch
on left
Switch
on right
Switch
on left
Switch
on right
Switch
on right
English
Type 8692, 8693
Electricalinstallation
X6 - M12 circular connector, 4-pole
Pin
Wire color*
Assignment
1
brown
Operating voltage +
3
blue
Operating voltage
* The indicated colors refer to the connection cable available as an
accessory (918038).
X6 - M12 circular connector, 4-pole (operating voltage)
*** For reasons of wire resistance compensation, connect
the Pt 100 sensor via 3 wires.
Always bridge Pin 3 and Pin 4 on the sensor.
24 V DC
GND

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

8693

Table des Matières