Output filter

Time constant
Time constant of output fi lter
To smoothen the current output, a low-pass filter with adjustable time con-
stant can be switched on. When there is a jump at the input (100 %), the
output level is at 63 % after the time constant has been reached.
The time constant can be set from 0 to 120 sec. If the time constant is set to
0 s, the current output follows the input.
Note:
The filter only acts on the current output and the current value of the
secondary display, not on the measurement display, the limit values, or the
controller!
Process variable
0 (4) - 20 mA
Time constant 0 ... 120 sec