8.2.2.8.3 Temperature Limits
The "Temperature Limits" submenu contains a number of readable parameters indicating
the limit values stored in the device for temperature monitoring purposes.
Mainboard temperature upper limit: Upper limit temperature of the amplifier's mainboard
Mainboard temperature lower limit: Lower limit temperature of the amplifier's mainboard
Processor temperature upper limit: Upper limit temperature of the processor
Processor temperature lower limit: Lower limit temperature of the processor
Temperature warning upper hysteresis: Temperature difference resulting in a warning
being canceled. The temperature must drop by at least the specified value for an
"Upper limit" warning to be canceled.
Temperature warning lower hysteresis: Temperature difference resulting in a warning
being canceled. The temperature must rise by at least the specified value for a
"Lower limit" warning to be canceled.
The following fields are not displayed if your force transducer does not have a tempera
ture sensor: C9C, U9C, U93A.
Nominal Temperature Overload Warning: Enables/disables warnings when the tempera
ture exceeds/falls below the nominal (rated) temperature of the transducer. Exceeding/
falling below the operating temperature range always results in a warning.
Transducer nominal temperature upper limit: Upper nominal (rated) temperature of the
transducer
Transducer nominal temperature lower limit: Lower nominal (rated) temperature of the
transducer
Transducer operational temperature upper limit: Upper limit temperature of the trans
ducer
Transducer operational temperature lower limit: Lower limit temperature of the trans
ducer
Index
Sub-
(hex)
index
(hex)
0x0056
0x00
0x0058
0x00
0x005E
0x00
0x005F
0x00
U10M
ELECTRICAL CONNECTION
Authoriza
Data type
tion
ReadOnly
Float32T
ReadOnly
Float32T
ReadOnly
Float32T
ReadOnly
Float32T
Data
Name
size
(bytes)
4
Mainboard
temperature
4
4
Processor
temperature
4
Description
Upper limit
Lower limit
Upper limit
Lower limit
59