8.2.2.7.4 Zero Setting
You can use the "Zero-Set" function in the software of your IO-Link master to set zero.
Measured data continues to be outputted after the electronics has zeroed.
The zero point is not saved permanently; if you disconnect the device from the supply
voltage it will have to be zeroed again.
Index
Sub
(hex)
index
(hex)
0x0C1B 0x00
0x0002
0x00
0x0002
0x00
8.2.2.7.5 Limit value switches (Switching Signal Channel 1 / Switching Channel 2)
There are two limit value switches that are executed as per the IO-Link Smart Sensor pro
file specification (B.8.3 Quantity detection). Each limit value switch is a main item in the
"Parameters" menu. Their operation is identical.
S
Switch 1: SSC.1 (Switching Signal Channel 1)
S
Switch 2: SSC.2 (Switching Signal Channel 2)
U10M
ELECTRICAL CONNECTION
Authorization Data type
ReadWrite
UIntegerT 1
ReadWrite
Float32T
Authoriz
Data
ation
type
Read
Float3
only
2T
Write
UInteg
er8T
Write
UInteg
er8T
Data
Name
size
(bytes)
Lowpass
Filter Mode
4
Lowpass
Filter cut-off
Frequency
Data
Name
size
(bytes)
4
Zero
Offset
1
Zero -
Set
1
Zero -
Reset
Description
Activate/
deactivate filter
and select filter
characteristic
0 - No filter
50 - Bessel filter
51 - Butterworth
filter
Input cut-off
frequency
System
Description
command
(hex)
Current zero
value, as
defined by
"Zero Setting"
0xD0
Triggers
zeroing
0xD2
Deletes the
zero memory