Baud rate confi-
IMPORTANT! Set the bus coupler node number and Baud rate before starting up
guration BK5200
the bus coupler.
1
2
3
The Baud rate is set using switches 7 and 8. The following table contains informa-
tion about the different Baud rate settings.
Baud rate setting
125 kBd
250 kBd
500 kBd
(Default) 125 kBd
4
50
0
x 1
0
x 10
Using the original screws, fit the interface lid back into its original position
Ensure that all devices and components have been switched off and discon-
nected from the mains
Ensure that the interface has been disconnected from the mains
Set MAC ID using DIP switches 1 to 6:
-
Switch 1 = least significant bit (2
-
Switch 6 = most significant bit (2
Using the original screws, fit the interface lid back into its original position
Example
Setting address 34:
-
Upper rotary selector switch S520:
4
-
Lower rotary selector switch S521:
3
0
)
5
)
The bit is set if the switch is in the ON
position
The MAC ID can be in the range 0 to
63.
1
2
3
4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5
6
7
8
-
-
off
off
-
-
on
off
-
-
off
on
-
-
on
on