Operating Instructions

8 Errors

8.1 Errors and warning messages (indicator flashes in display segments A and B, Table 5)
Indicator A
Indicator B
OL
OVERPRESS
UL
UNDERPRES
ERR1
GEN.ERROR
ERR2
SHORTOUT1
SHORTOUT2
ERR3
OVERVOLTG
ERR4
LOW VOLTG
ATT1
SHIFT RP1
SHIFT RP2
ATT2
ADJ>LIMIT
LOCK
KEYLOCKED
Table 5: Errors and warning messages
8.2: Diagnostic output behavior in the event of an error
Switching output 2 (if available) can be configured as a diagnostic output ("OU2" function).
7 4
O p e r a t i n g I n s t r u c t i o n s | S I C K
Status
Description
Error
Applied pressure > upper limit of measuring range
Error
Applied pressure < lower limit of measuring range
Error
General error
Error
Short-circuit at one of the two outputs
Error
Applied supply voltage > 30 V DC
Error
Applied supply voltage < 17 V DC
Warning
Switching point setting made by the operator below
the reset point that is set. The reset point is auto-
matically set below the new switching point with the
smallest possible hysteresis.
Warning
Displayed if the applied pressure during zero
adjustment lies outside the permitted limit of 5%
of the range
Warning
Displayed if an attempt is made to access the
programming mode while the input lock is active
8 Errors
Action required
Set pressure to within
measuring range
Set pressure to within
measuring range
Contact SICK
Remove the short-circuit
Make the correct settings for
the supply voltage
Make the correct settings for
the supply voltage
Acknowledge by pressing the
<enter> pushbutton
Acknowledge by pressing the
<enter> pushbutton
Enter the password or unlock
via IO-Link if parameter entry
has been locked by IO-Link
8017612/YSZ4/2016-02-09 | PAC50
Subject to change without notice