Manual Operation Without Power Supply - Burkert 1067 Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4 OPERATION

4.6 Manual operation without power supply

The solenoid valves integrated in the positioner can be manually operated without a power supply
by using rotary knobs. These rotary knobs (red) are accessible when the bonnet of the unit is opened.
They are located immediately behind the electrical terminals. Two rotary knobs are provided on the
type for single-acting actuator (Fig. 38).
Fig. 38 Manual operation
Preconditions for manual operation using the rotary knobs.
- The power supply of the unit must not be connected under any circumstances.
- The pneumatic connections and the pressure supply must be present.
Settings
All rotary knobs are in position 0 (normal position):
Drive is vented.
In this case, in the design for double-acting actuating drives, the chamber connected to terminal A1
is vented and the chamber connected to terminal A2 is supplied with air.
All rotary knobs are in position 1:
Drive is supplied with air.
In this case, in the design for double-acting actuating drives, the chamber connected to terminal A1
is supplied with air and the chamber connected to terminal A2 is vented.
Caution!: All rotary knobs must be returned to the 0 position before connecting the power supply to
the positioner.
POSITIONER 1067
E-36-

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Positioner 1067

Table des Matières