4 OPERATION
To perform a setting within the X-SENS and INPUT menu items, briefly press the MANUAL/
AUTOMATIC key again. One of the menu sub-items then appears in the display. It is possible to
switch back and forwards between these sub-items, each of which describes a possible setting, by
again pressing the arrow keys. The actual setting is carried out by pressing the MANUAL/ AUTOMATIC
key on the selected menu sub-item.
Fig. 25 Signification of the menu options in the main menu
Basic function
X-SENS
- DIRECT
- LEVER
INPUT
- 4 ... 20 MA
- 0 ... 20 MA
- 0 ... 10 V
ADDFUNCT
AUTOTUNE
END
Under the menu option X-SENS, indicate whether the mechanical transmission of path information
from the positioner to the feedback/positional transducer is based on a linear or sinusoidal relationship.
A sinusoidal relationship results if the lever mechanism is used for the transmission of path information
(cf. section 3.1.1). In this event, when LEVER is confirmed an internal linearization takes place by
means of an approximated sinusoidal function.
The ADDFUNCT menu item can be skipped on the initial setting up. It is used only to configure
additional functions.
The AUTOTUNE menu item is used to start the programme for automatic parametering of the
positioner. This automatically triggers the following functions:
- Matching the sensor signal to the (physical) stroke of the control valve used.
- Determining parameters of PWM signals for control of the internal solenoid valves.
- Optimum adjustment of the control parameters of the position controller (target function: fastest
possible movement to the set position without hunting).
The programme for automatic parametering is started by setting the AUTOTUNE menu item in the
main menu and then pressing the MANUAL/AUTOMATIC key and holding for 5 seconds. TUNE is
displayed with a countdown from 5 to 0. The word AUTOTUNE then flashes for approximately 30 to
120 seconds (depending on the actuator volume). After the flashing ends, the message TUNE END
is displayed.
Note: In case of complete delivery of a valve fitted with a positioner, the AUTOTUNE function has
already been run through in factory. In order to obtain the best accuracy, it is recommended to run
the AUTOTUNE function once more before putting the valve in operation.
If it is not possible to fully complete the AUTOTUNE routine, an error message is displayed (refer to
the list of error messages in part 5).
Associated settings
Type of information transfer between the actuator and travel measuring
system (factory-set to DIRECT)
- Linear relationship
- Sinusoidal relationship (use of a lever)
Specification of selected unit signals
- Unit signal current 4 ... 20 mA
- Unit signal current 0 ... 20 mA
- Unit signal voltage 0 ... 10 V
Configuration of additional functions
Actuation of automatic adaptation of the actuator to the valve
End of menu