Messages; Error Messages - HYDAC ELECTRONIC ENS 3000 Notice D'utilisation

Masquer les pouces Voir aussi pour ENS 3000:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENS 3000

12 Messages

12.1 ERROR MESSAGES

If an error is detected, a corresponding error message appears that must be
acknowledged by pressing any key.
Possible error messages:
The switch points and hysteresis values have been set in such a way that the
E.01
resulting switch-back point is no longer within the permitted setting range.
Example:
Switching point has been set to 21.0 cm, the hysteresis to 23.0 cm.
Correct the settings.
Action:
A data error was detected in the saved settings. This could be due to strong
E.10
electromagnetic interference or a component fault.
Check all settings (programming enable, switch points, switch-back points and
Action:
basic settings) and correct them, if necessary. If the error occurs frequently,
please contact the HYDAC Service Department.
Implausible measuring values have been reported from the level sensor for a long
E.20
period.
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.
A communication error was detected within the level sensor.
E.21
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.
An internal communication error to the temperature sensor (optional) was
E.22
detected.
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.
Status 19.09.2018
HYDAC ELECTRONIC GMBH
Page24
Part No. 669849

Publicité

Table des Matières
loading

Table des Matières