ENS 3000
12 Messages
12.1 ERROR MESSAGES
If an error is detected, a corresponding error message appears that must be
acknowledged by pressing any key.
Possible error messages:
The switch points and hysteresis values have been set in such a way that the
E.01
resulting switch-back point is no longer within the permitted setting range.
Example:
Switching point has been set to 21.0 cm, the hysteresis to 23.0 cm.
Correct the settings.
Action:
A data error was detected in the saved settings. This could be due to strong
E.10
electromagnetic interference or a component fault.
Check all settings (programming enable, switch points, switch-back points and
Action:
basic settings) and correct them, if necessary. If the error occurs frequently,
please contact the HYDAC Service Department.
Implausible measuring values have been reported from the level sensor for a long
E.20
period.
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.
A communication error was detected within the level sensor.
E.21
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.
An internal communication error to the temperature sensor (optional) was
E.22
detected.
Acknowledge the error message by pressing any key. If the error message
Action:
continues to be displayed, please contact our service department.