11 Error messages

If an error is detected, then a corresponding error message appears which must be acknowledged
by pressing any key. Possible error messages are as follows:
The switching points and hystereses have been set in such a way that the resulting
E.01
switch-back point is no longer within the permissible setting range.
Example:
Switching point is set to 180 bar, the hysteresis to 200 bar.
The setting is not correct since the resulting switch-back point is smaller than the
switching point: the error message is displayed.
Correct the settings.
Action:
A data error has been detected in the saved settings. Possible causes are strong
E.10
electromagnetic interference or a component fault.
Check all the settings (programming enables, switching points, switch-back points
Action:
and basic settings) and correct these if necessary. If the errors occur frequently,
please contact Hydac Service.
An error has been detected in the stored calibration data. Possible causes are strong
E.12
electromagnetic interference or a component fault.
Disconnect the unit from the supply voltage and then re-connect. If the error
Action:
message is still displayed, the unit must be returned to the manufacturer for re-
calibration or repair.