ENS 3000
18.2 HYDRAULIC POWER UNIT: MINIMUM FLUID LEVEL MONITORING WITH
ADVANCE WARNING AND MINIMUM TEMPERATURE MONITORING
In this example application, an advance warning should be given when the fluid level
reaches 30 cm and tank refilling should be started. The temperature also must not fall
below a certain limit. If, for example, a temperature of
20°C is reached, a "stop" signal will appear. Furthermore, the temperature will be
transferred to an SPS card as a 4 .. 20 mA signal.
For realization of this function as described in the example,
the following settings in the menu and on the switching points of ENS 3000 must be
effected:
Menu item
Switching output S.S.1 assignment
Switching mode S.m. 1
Switching direction S.d. 1
Switch-on delay Ton 1
Switch-off delay Toff 1
Switching output S.S.2 assignment
Switching mode S.m. 2
Switching direction S.d. 2
Switch-on delay Ton 2
Switch-off delay Toff 2
Analogue output S.ouT assignment
Analogue output ouTP
Switching point settings
Switching output S.P.1
Hysteresis switching output Hi.1
Switching output S.P.2
Hysteresis switching output Hi.2
Status 19.09.2018
Selection
niv
SP
off
TEMP
SP
on
TEMP
MAMP
Numerical value
30.5
0.5
20.5
0.5
HYDAC ELECTRONIC GMBH
Numerical value
1
1
1
1
Part No. 669849
Page35