Error Messages

If an error is detected a corresponding error message is displayed which must be
acknowledged by pressing any key. Possible error messages are as follows:
E.01
The switching points and hysteresis values have been set so that the resulting
switch-back point is no longer within the permissible setting range.
Example:
The switching point is set to 50°C, the hysteresis to 100°C .
Corrective action:
A data error has been detected in the saved settings. Possible causes: strong
E.10
electromagnetic interference or a component fault.
Corrective action: Check all settings (programming enables, switching points, switch-back
points and basic settings) and correct them, if necessary. If the error occurs
frequently, contact HYDAC's Service Department.
A communication error has been detected in the unit. Possible causes: strong
E.21
electromagnetic interference or a component fault.
Corrective action:
the error persists, contact HYDAC's Service Department.
11.

Wiring Diagrams

11.1

Supply Voltage and Switching Outputs

Model with 2 switching outputs
4-pole M12x1 connection
1
+
9 - 35 V
ETS 3XX6-2
3
-
Model with 2 switching outputs and
1 analogue output
5-pole M12x1 connection
4
1
+
ETS 3XX8-5
18.-.35 V
5
3
-
2
Status 17.08.2016
Correct the settings.
Disconnect the unit from the supply voltage and reconnect it again. If
Imax. 1.2 A
4
SP 1
Imax. 1.2 A
2
SP 2
Imax. 1.2 A
SP 1
Imax. 1.2 A
SP 2
Analogue
signal
RL
HYDAC ELECTRONIC GMBH
Model with 1 switching output and
1 analogue output
4-pole M12x1 connection
1
+
ETS 3XX6-3
18 - 35 V
3
-
Page 13
Imax. 1.2 A
4
SP 1
Analogue
2
signal
RL
Part No.. 669859

Publicité