3 INSTALLATION
The transmitter type 8025 can easily be connected to a PLC, independently of the respective
version (see fig. 3.7).
8025
Fig. 3.7 PLC-connection

3.4.2 Type 8025 with relays

The electrical wiring ensues via 2 cable
glands. Remove cover, pull cable through
PG 13.5 and wire according to following pin
assignment (Fig. 3.8):
1: Current output 4...20 mA
2: L+ (12...30 VDC)
3: L-
4: Earth (earth lug)
5: B pulse ouput
6: A pulse output
7: Relay 2
8: Relay 2
9: Relay 1
10: Relay 1
Note: PLC-connection. Depending on the PLC-version, the switch 1 on the circuit board
must be put to position A or B (see fig. 3.8 and fig. 3.9). In this case remove the strap
(see fig. 3.8).
If the current output 4...20 mA is not used, it must be connected to L- with
!
switch 1 in position A. For that purpose use the strap (see fig. 3.8).
V+
2
L+
PLC
L-
3
0V
FLOW TRANSMITTER 8025
8025
2
L+
L-
3
2 Sensor with coil
1 Hall sensor
Sensor connection
7 8
Fig. 3.8 Pin assignment of
transmitter 8025 with relays
E-14-
V+
PLC
0V
Strap
1 2 3 4 5 6
Switch 1
9 10
8025 - 8025RR