Burkert 8025 Notice D'utilisation page 56

Transmetteur de debit
Masquer les pouces Voir aussi pour 8025:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3 INSTALLATION REED
3.7 Electrical Wiring 8025 with relay Reed Compact Version
The electrical wiring ensues via 2 cable
glands.
Remove cover, pull cable through PG 13.5
and wire according to pin assignment (see
fig. 3.5).
1: Current output 4...20 mA
2: L+ (12...30 VDC)
3: L-
4: Earth (earth lug)
5: Relay
6: Relay
If the current output 4...20 mA is
!
not used, it must be connected to
L- with switch 1 in position A. For that
purpose use the strap (see fig. 3.16).
3.7.1 Electrical wiring 8025 with relay Reed to an SPS
The connection of the sensor is identical to the standard version.
Refer to § 3.5 (terminal 4-5)
3.7.2 Electrical wiring with power supply of 230/115 VAC (option)
Remove the cover of the device, the powersupply board is in the bottom of the housing.
Pull supply cable through PG 13,5 and wire according to fig. 3.17.
The outputs (current and relay) remain at same position.
If the current output is used, remove the strap (fig. 3.16).
8025 - 8025RR
FLOW TRANSMITTER 8025
Swich 1
2 Sensor with coil
1 Hall Sensor
Sensor connection
8025 REED
Fig. 3.16 Pin assignment
transmitter 8025 with relay Reed
E-19-
Strap
1 2 3 4
5 6

Publicité

Table des Matières
loading

Table des Matières