For battery cabinets, keep the same distances as for the
UPS, which are configured by the system.
Minimum dimensions for ventilating a system.
•
Power
7,5 - 20 kVA
10 cm.
Tab. 4. Minimum installation distances.
5.1.6.3. Immobilisation and levelling of the unit
• The
SLC CUBE4
7.5 kVA to 20 kVA
wheels with brakes and stabilising supports and elements.
The UPS cabinet has wheels with brakes and stabilising
supports (see Fig. 1), the tall battery cabinet has wheels
with brakes, stabilising elements and supports (Fig. 9),
while the small battery cabinet has just wheels with
brakes (Fig. 8).
• The purpose of the stabilising elements mentioned in the
unpacking section is to immobilise, level and stabilise the
metal cabinet once it has been put in place.
• To immobilise the tallest battery cabinets using the sta-
bilising elements, it is necessary to loosen the elements
by hand, turning them in anticlockwise direction until they
touch the floor, and using a spanner, loosen them by an-
other half turn to immobilise the metal cabinet, ensuring
the correct levelling.
Fig. 31 shows how the stabilising elements must be in the ends.
B
Cabinet
UPS with
batteries
A
C
A
Fig. 29. Minimum peripheral dimensions for ventilating the UPS
tower version.
B
Battery
Battery
cabinet
cabinet
UPS no. 1
UPS no. 2
A
C
A
Fig. 30. Minimum dimensions for ventilating a UPS tower version
system in parallel..
USER MANUAL
A
B
C
10 cm.
40 cm.
UPS
series feature
B
UPS
UPS
battery
cabinet
cabinet
A
C
A
Cabinet
Cabinet
UPS no. 1
UPS no. 2
A
Ax2
Original position from
factory.
Fig. 31. Stabilising elements for the unit/battery module.
• Unit and battery maintenance is the responsibility of the
T.S.S. or authorised staff.
The batteries are always accessed from the side on all
units and/or battery modules. Before any handling, observe
the indications on the label attached to each one.
5.1.6.4. Preliminary considerations before
connection
• The description of this manual refers to the connection of
terminals and switch operations that are only available in
certain versions or units with extended autonomy. Ignore
the related operations if your unit does not have them.
• Follow and observe the instructions described in this sec-
tion relating to the installation of a single unit or a parallel
system.
• Protection or external manual bypass panel:
It is recommended to have an external manual bypass
panel provided with input, output, static bypass (the
latter only in the
bypass protection devices in single installations.
For parallel systems of up to two units, it is highly
recommended to have a protection board and it is es-
UPS
cabinet
A
A
Cabinet
Cabinet
UPS no.3
UPS no. 4
Ax2
Ax2
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-
Pressed against the floor.
SLC CUBE4 B
version) and manual
B
Battery
Battery
cabinet
cabinet
UPS no. 1
UPS no. 2
A
C
A
Battery
Battery
cabinet
cabinet
UPS no. 3
UPS no. 4
A
A
A
A
99