7.4.2. ADVANCED configuration - Password
10 kVA
Bypass Mode
GENERAL
PASSWORD
ADVANCE
Password remain
HOME
CONTROL
7.4.2.1. Advanced user configuration menu
10 kVA
Bypass Mode
ELECTRIC
BATT
MISCELLANEOUS
HOME
CONTROL
7.4.2.1.1. ELECTRIC submenu
10 kVA
Bypass Mode
Output VOL.
Output FRE
ELECTRIC
CVCF Mode
BATT
Bypass Forbid
MISCELLANEOUS
NeutralLineCheck
ISO Compensation
HOME
CONTROL
USER MANUAL
2020.11.04
11:56:35
0
Min.
MEASURE
SETTING
INFO
2020.11.04
11:56:35
MEASURE
SETTING
INFO
230 V
Auto
Disabled
Disabled
Verif.
0. 0%
MEASURE
SETTING
INFO
The password (4 digits) must be entered to access the "ADVANCED"
settings menu.
There are two types of restriction, one at the advanced user level
and the other at the maintenance user level.
Advanced user
•
To access the "Advanced user" configuration menu, the default pass-
word is "1234".
If the password entered is correct, the page will jump to the con-
figuration screen. If the password is incorrect, you will be asked to
enter it again.
DATALOG
Maintenance user
•
There is a second password for qualified technical staff to access
certain maintenance functions that are not available for basic users.
Advanced user configuration menu:
There are three submenus under user password "1234":
ELECTRIC, BATT and MISCELLANEOUS.
DATALOG
Output VOL: select the nominal output voltage.
•
2020.11.04
11:56:35
There are four options, 208 V, 220 V, 230 V* and 240 V.
Output FRE: select the nominal output frequency.
•
AUTO*: the output frequency is auto-detected according to
the normal input when the unit is connected to the mains. If
it is between 46 and 54 Hz, it will be set to 50 Hz, and it if it
between 56 and 64 Hz, it will be set to 60 Hz.
50 Hz: the output frequency is set to 50 Hz.
60 Hz: the output frequency is set to 60 Hz.
DATALOG
CVCF Mode: Frequency converter function (see description of
•
CVCF mode in section 4.5.6).
Enabled: the CVCF function is enabled. The output fre-
quency will be set to 50 Hz or 60 Hz according to the output
frequency setting. The input frequency can be between 40
Hz and 70 Hz.
Disabled*: the CVCF function is deactivated. The output
frequency will be synchronised with the bypass frequency
within the 45 - 55 Hz ranges for the 50 Hz system or within
55 - 65 Hz for the 60 Hz system.
Bypass Forbid:
•
Enabled: When selected, the static bypass is disabled,
not allowing the switch to bypass mode in the event of an
anomaly, such as overload/fault.
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-