7.4.2.1.2. BATTERY submenu
10 kVA
Bypass Mode
BATT Warning VOL
Shutdown VOL
ELECTRIC
BATT
BATT Parameters
MISCELLANEOUS
BATT AH
BATT groups
BATT Mode Work Time
HOME
CONTROL
7.4.2.1.3. MISCELLANEOUS submenu
10 kVA
Bypass Mode
Auto Restart
ELECTRIC
Shutdown Delay
Restore Delay
BATT
New Password
MISCELLANEOUS
HOME
CONTROL
Tab. 8. Screens and contents of the Settings menu on the control
panel..
USER MANUAL
2020.11.04
11:56:35
11. 0 V
15. 0 V
HIGH
LOW
10. 5 V
9
1
999 Min
Disabled
MEASURE
SETTING
INFO
Disabled
0 Min
0 Min
****
MEASURE
SETTING
INFO
BATT Warning VOL:
•
High: high battery voltage warning level. The setting range
is from 14.0 V to 15.0 V*. 15 V is the default configuration.
Low: low battery voltage warning level. the setting range is
from 10.1 V to 14.0 V. 11 V is the default value. This setting
value must be greater than the "Shutdown voltage" setting
due to low battery voltage.
Shutdown VOL: when the battery voltage is less than this in
•
battery mode, the UPS will shut down automatically. the setting
range is from 10.5 V to 12 V. 10.5 V is the default configuration.
DATALOG
(This configuration is only available for the B1 long autonomy
model). For standard units, the shutdown voltage level due to
low battery depends on the output load (see the electrical char-
acteristics in ).
BATT Parameters:
•
BATT AH: battery capacity configuration.
BATT Groups: configuration of the no. of groups of bat-
teries in parallel.
BATT Mode Work Time: It lets you limit the autonomy
time.
Automatic Restart (Hot Standby):
•
2020.11.04
11:56:35
Enabled: if this function is activated, the UPS will start au-
tomatically in online mode.
Disabled*: the UPS does not start automatically in on-
line mode. It remains in bypass mode or standby mode
depending on the configuration until the order is given to
switch to online mode.
Shutdown Delay: the UPS will shut down after the configured
•
minutes. The countdown will start after confirming the value.
DATALOG
Restore Delay: the UPS will restart automatically in the se-
•
lected configuration minutes after the UPS has shut down.
New Password: it lets you change the advanced user pass-
•
word.
*Default settings.
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-