Tab. 9. Screens and contents of the Info menu on the control panel.
USER MANUAL
PARAMETER:
Line VOL Range: acceptable line input voltage range.
•
Line FRE Range: acceptable line input frequency range.
•
Bypass VOL Range: acceptable input voltage range for bypass
•
mode.
Bypass FRE Range: acceptable input frequency range for by-
•
pass mode.
ECO VOL Range: acceptable input voltage range for ECO mode.
•
ECO FRE Range: acceptable input frequency range for ECO
•
mode.
BATT Mode Work Time: maximum discharge time in battery
•
mode.
BATT Warning VOL:
•
HIGH: level of battery voltage that activates the high bat-
tery warning.
LOW: level of battery voltage that activates the low battery
warning.
Shutdown VOL: level of battery voltage that shuts the UPS
•
down due to low voltage.
Shutdown Delay: the UPS will shut down in the configuration
•
minutes. The countdown will start after confirming via the pop-
up screen.
Restore Delay: the UPS will restart automatically in the con-
•
figuration minutes after the UPS has shut down.
BATT Number : shows the number of batteries.
•
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-
121